Why Choose Our Vacuum Circuit Breakers
- Over 20 years of experience in manufacturing vacuum circuit breakers
- Fully certified to international grid standards including IEC,CE,
- Full-cycle engineering support from selection to installation.
- Flexible OEM/ODM solutions can meet customized size requirements.
- Designed for quickly extinguishing arcs and providing overload protection.
- Factory direct sales, fast quotes, and free technical consultation.
Your Reliable Vacuum Circuit Breaker Manufacturer
With over 20 years of experience in electrical engineering, Lugao has delivered vacuum circuit breakers to medium-voltage power systems in more than 30 countries worldwide. Our high-quality vacuum interrupters, contacts, and operating mechanisms safety of operation and eliminate the risk of fire or oil leakage. Vacuum circuit breakers can interrupt high fault currents within milliseconds, preventing transformer damage and grid outages.
Contact Lugao’s engineering team today for your customized layout drawings and factory wholesale pricing.
Manufacturing the Electrical Products You Need
Lugao offers comprehensive, one-stop electrical solutions; we customize electrical products to meet your project requirements based on the single-line diagrams you provide.

Suitable for indoor switchgear and substations, used for the protection and control of electrical equipment.

Suitable for overhead transmission lines and outdoor substations. Used for switching load current, overload current, and short-circuit current.
Why You Need Vacuum Circuit Breakers for Your Grid
Vacuum circuit breaker is a circuit breaker that uses vacuum as the arc-extinguishing medium.Including those of fast fault interruption, long service life, and low maintenance. It is typically used in medium-voltage power systems to protect electrical equipment from short circuits and overloads.

Core operating mechanism and sealing electrode require no mechanical adjustment or gas replenishment, reducing maintenance costs.

Each vacuum circuit breaker undergoes strict power-frequency withstand voltage and routine insulation testing.Embedded poles protect circuit breakers from internal flashover.

Utilizing high-quality insulation materials, it can operate stably even in extreme industrial environments such as high altitudes and coastal areas.

It will not undergo thermal or mechanical deformation when dealing with short-circuit current, giving the entire switchgear assembly an extremely high fault tolerance margin.
Strictly Comply with the Specified Parameters
Our vacuum circuit breakers undergo comprehensive type testing according to IEC and CE standards. Therefore, we can provide you with complete technical documentation and design strictly according to your specifications, ensuring your power distribution projects pass municipal power grid acceptance and meet bidding requirements, avoiding project delays due to unqualified equipment test reports.


Longer Service Life, Lower Maintenance Costs
Frequent maintenance increases costs and leads to downtime. Lugao’s vacuum circuit breakers feature durable vacuum interrupters and reliable operating mechanisms; as no air medium is involved, the arc is rapidly extinguished at current zero, and dielectric strength recovers extremely quickly. High electrical conductivity, combined with resistance to arc erosion and contact welding, ensures extended mechanical and electrical service life, minimal contact wear, and reduced maintenance requirements.
Technical Knowledge Center
Get access to our comprehensive product catalog to learn about complete technical specifications, design, and configuration options.
Download our certified international certificates and type test reports to inspect our factory.
Watch our factory online and explore the manufacturing process of electrical equipment.
Your Trusted Vacuum Circuit Breaker Manufacturer


From machining and assembly to quality inspection, every detail of Lugao’s vacuum circuit breakers is rigorously controlled by our experienced engineering team. Our testing center conducts mechanical durability tests, power frequency withstand voltage tests, and loop resistance tests on each vacuum circuit breaker to protect electrical equipment from short circuits and overloads, ensuring it meets the operational requirements of power distribution networks in substations, industrial facilities, and other applications.
Applications of Vacuum Circuit Breaker

Vacuum circuit breakers provide switching and fault protection for substations and distribution networks, enhancing grid stability and reducing the risk of power outages.

Vacuum circuit breakers protect electrical equipment such as motors and transformers from short circuits and overloads, ensuring the normal operation of industrial facilities.

Providing uninterrupted power supply for critical facilities such as airports, hospitals, office buildings, and commercial complexes.

Vcbs provide safe grid-connection control and feeder protection for photovoltaic or wind power projects, while also isolating feedback surges.
- ZW32-12 Technical Parameters
- VS1-24 Technical Parameters
- ZN85-40.5 Technical Parameters
| project | Unit | Parameter |
| Rated voltage | kV | 12 |
| Rated frequency | Hz | 50 |
| Rated current | A | 630 |
| Rated short-circuit breaking current | kA | 20 |
| Rated peak withstand current (peak) | kA | 50 |
| Rated short-time withstand current | kA | 20 |
| Rated short-circuit making current (peak value) | kA | 50 |
| Mechanical life | 次 | 10000 |
| Rated short-circuit breaking current breaking times | 次 | 30 |
| Power frequency withstand voltage (1min): (wet) (dry) phase-to-phase,to ground/fracture | kV | 42/48 |
| Lightning impulse withstand voltage (peak value) phase-to-phase,to ground/fracture | kV | 75/85 |
| Secondary circuit 1min power frequency withstand voltage | kV | 2 |
| Dynamic and static contacts allowable cumulative thickness of wear | mm | 3 |
| Rated current of overcurrent release | A | 5 |
| Current transformer current ratio | 200/5 400/5 600/5 | |
| Contact Spacing | mm | 9±1 |
| Contact overtravel | mm | 2±0.5 |
| Average opening speed | m/s | 1.2±0.3 |
| Average closing speed | m/s | 0.6±0.2 |
| Opening time | ms | 20~40 |
| Closing time | ms | 30~60 |
| Closing bounce time | ms | ≤2 |
| Three-pole closing and opening of different periods | ≤2 | |
| DC resistance of each phase loop | μΩ | ≤80(With isolation as ≤150) |
| 序号 | Itemfrom | unit | parameter |
| 1 | rated voltage | kV | 24 |
| 2 | Rated short-time power frequency withstand voltage (1min) | kV | 65 |
| 3 | Rated lightning impulse withstand voltage (peak) | kV | 125 |
| 4 | rated frequency | Hz | 50 |
| 5 | rated current | A | 630/1250 |
| 6 | Rated short-circuit breaking current | kA | 25、31.5 |
| 7 | Rated short-time withstand current | kA | 25、31.5 |
| 8 | Rated short-circuit duration | s | 4 |
| 9 | Rated peak withstand current | kA | 63/80 |
| 10 | Rated short-circuit closing current | kA | 63/80 |
| 11 | Secondary circuit power frequency withstand voltage (1min) | V | 2000 |
| 12 | Rated breaking current of single/back-to-back capacitor bank* | A | 630/400 |
| 13 | Opening time | ms | ≤50 |
| 14 | Closing time | ms | ≤70 |
| 15 | mechanical life | time | M2级 10000(630-1250、31.5) |
| 16 | Electrical lifespan | time | E2级 |
| 17 | Allowable cumulative thickness of wear for dynamic and static contacts | mm | 3 |
| 18 | Rated closing operation voltage | V | AC110、AC220 DC110、DC220 |
| 19 | Rated opening operation voltage | ||
| 20 | Rated voltage of energy storage motor | ||
| 21 | Rated power of energy storage motor | W | 90 |
| 22 | Energy storage time | S | ≤15 |
| 23 | Contact opening distance | mm | 13±1 |
| 24 | Overtravel | mm | 3±1 |
| 25 | Contact closing bounce time | ms | ≤2 |
| 26 | Three phase asynchronous opening and closing | ms | ≤2 |
| 27 | Average opening speed | m/s | Contact stiffness:6mm,0.9~1.7 |
| 28 | Average closing speed | m/s | 6mm~Contact just closed 0.6~1.0 |
| 29 | Opening rebound amplitude | mm | ≤3 |
| 30 | Main electrical circuit resistance | μΩ | ≤45(630) ≤35(1250A) |
| 31 | Contact closing contact pressure | N | 3100~3700 |
| 32 | Rated operating sequence | Min-0.3s HeFen-180s HeFen |
| Serial Number | project | unit | data |
| 1 | Rated voltage | KV | 40.5 |
| 2 | 1-minute power frequency withstand voltage (effective value) | kV | 95 |
| 3 | Lightning impulse withstand voltage (peak value) | kV | 185 |
| 4 | Rated frequency | Hz | 50 |
| 5 | Rated current | A | 1250,1600,2000 |
| 6 | Rated short-time withstand current | kA | 25,31.5 |
| 7 | Rated peak withstand current | kA | 63,80 |
| 8 | Rated short-circuit duration | S | 4 |
| 9 | Rated short-circuit breaking current | kA | 25,31.5 |
| 10 | Rated short-circuit closing current | kA | 63,80 |
| 11 | Rated operating sequence | O-0.3s-CO-180s-CO | |
| 12 | Cut off time | ms | <80 |
| 13 | Rated short-circuit breaking current breaking times | order | 20 |
| 14 | Single capacitor bank breaking current | A | 630 |
| 15 | Back to back capacitor bank breaking current | A | 400 |
| 16 | Rated operating voltage | V | AC110,220;DC110,220 |
| 17 | Mechanical lifespan | order | 10000 |
Testimonials
Vacuum circuit breakers utilize the principle of vacuum arc extinguishing to interrupt fault currents by separating contacts internally. The vacuum rapidly extinguishes the arc, enabling the circuit to be safely disconnected.
Indoor circuit breakers are typically installed in medium-voltage metal-enclosed switchgear cabinets, featuring a compact design and compatibility with KYN28 switchgear models. Outdoor circuit breakers are usually pole-mounted, employing higher creepage distances to withstand harsh outdoor environments.
Vacuum circuit breakers extinguish arcs within a sealed vacuum chamber, eliminating the need for gas monitoring, simplifying maintenance, and reducing operating costs. They are typically used in medium-voltage power distribution projects. SF6 circuit breakers, on the other hand, use sulfur hexafluoride gas, requiring continuous pressure monitoring and recovery treatment. They are typically used in high-voltage transmission networks.
Choosing the right vacuum circuit breaker depends on system voltage, rated current, short-circuit breaking capacity, installation method, and project specifications. You can provide drawings, and our engineering team will assist you with the selection free of charge.
Vacuum circuit breakers are typically available in rated voltages of 3.6kV, 7.2kV, 12kV, 17.5kV, 24kV, 36kV, and 40.5kV. Selection should be based on the power distribution system requirements and electrical standards.
No, the vacuum interrupter has a sealed structure and requires almost no maintenance. The spring operating mechanism requires basic cleaning and lubrication approximately every two years or after a certain number of operations.
VCBs are commonly used in power substations, industrial plants, and medium-voltage switchgear systems—places requiring reliable switching and fault protection.
Lugao’s professional production lines have efficient manufacturing capabilities, and the delivery time for customized vacuum circuit breakers is about 2 weeks. We also maintain a certain amount of inventory for emergency use.
Yes, we will provide detailed product documentation. Please contact us immediately if you encounter any product issues.
We accept international payment methods such as Telegraphic Transfer (T/T) and Letter of Credit (L/C); 30% T/T payment before mass production, the rest 70% payment before shipment.
Related Product
Sf6 Gas Insulated Current TransformerAn SF6 gas insulated current transformer is a high-voltage current transformer that utilizes SF6 gas as an insulating medium, designed for use in power system measurement and protection.
The JDQXF SF6 Gas Insulated Voltage Transformer is an inverted/gas-insulated electromagnetic voltage transformer designed for high-voltage power grids.
Outdoor HV SF6 Circuit BreakerOutdoor HV SF6 circuit breakers are SF6-insulated control and protection devices used in outdoor substations and on transmission lines, capable of interrupting high short-circuit currents.
An HV middle type SF6 circuit breaker is an SF6 circuit breaker in which the arc-extinguishing chamber and live components are housed within a grounded metal tank.
The GW4 outdoor high-voltage (HV) disconnector switch is a double-column, horizontally opening outdoor HV disconnector, primarily used for making or breaking circuits under no-load conditions.